CC-Link title image

CC-Link

PLC Sequence Control Course logo

PLC Sequence Control Course

PLC Sequence Control Course recommended materials
PLC Sequence Control Course recommended materials

CC-Link is a fieldbus network developed by Mitsubishi Electric that allows robot controllers, solenoid valve manifolds, and numerous other devices to be connected with just 4 cables. This page explains with video the complete setup procedure — wiring, station number configuration, GX Works2 network parameter settings, and device assignment verification — without requiring any ladder program.

Created: October 10, 2017
Updated: May 23, 2026

What Is CC-Link?

CC-Link is a fieldbus network developed by Mitsubishi Electric Corporation. Connecting robot controllers and large numbers of solenoid valves normally requires extensive wiring, but CC-Link allows connection with just 4 cables, dramatically reducing wiring work.

There are different variants of CC-Link. Types with suffixes such as CC-Link IE and CC-Link/LT are distinct from standard CC-Link. All devices connected on a network must use the same CC-Link type.

CC-Link system configuration diagram (master station and local station connections)

CC-Link is especially effective for connecting robot controllers. Standard I/O wiring requires many individual wires, but CC-Link completes the connection by passing just 4 dedicated cables. When additional CC-Link devices are present, simply continuing the cable to the next device completes the wiring.

CC-Link Wiring

The following uses the Q series CC-Link unit "QJ61BT11N" as an example. CC-Link always consists of a master station and local stations (slave stations). The PLC acts as the master station.

CC-Link wiring diagram (master station and remote I/O unit connections)

Connect each unit with CC-Link cables, and always attach terminating resistors at both ends of the connection. Terminating resistors are included with CC-Link devices. Remote I/O units are input/output units compatible with CC-Link, so no separate I/O units are required.

CC-Link Configuration

Understanding the following concepts is important when configuring CC-Link.

CC-Link master station and local station configuration diagram

A station number is an address that identifies each device on the network. The master station is assigned station number 0; local stations are assigned numbers 1 and above. Duplicate station numbers prevent a device from joining the network, so each device must have a unique number.

Occupied station count is the setting for how many station numbers to allocate to one local device. A higher occupied station count provides more functionality, but since the CC-Link station number limit is 64, fewer total devices can be connected. Check each device's manual to determine the occupied station count.

CC-Link station number and occupied station count settings screen

Actual Configuration Workflow

CC-Link initial configuration procedure: ① Connect devices with CC-Link cables and attach terminating resistors at both ends → ② Set communication speed (same value on all devices) → ③ Configure network parameters in GX Works2 → ④ Verify device assignment one unit at a time using the device usage list

First, physically connect the devices together with CC-Link cables. When multiple devices are present, connect them in a chain: master (PLC) → Device 1 → Device 2. Then attach the included terminating resistors at the very beginning and very end of the connection.

After connecting, set the CC-Link communication speed. Local devices typically have their own speed settings — set all of them to the same value. Using the maximum speed supported by all devices is recommended. For example, if all connected devices support up to 10 Mbps, set 10 Mbps. If even one device supports only up to 5 Mbps, set 5 Mbps for all.

*Note: With very long cables or many relay points, reducing the speed may be necessary to avoid communication errors.

Configuration methods vary by device: some units have physical rotary switches on the front panel, while others are configured via computer connection. The "QJ61BT11N" uses rotary switches on the front panel. Set the station number to 0 to designate it as the master station using the STATION NO switch.

CC-Link unit

The communication speed is set using the "MODE" rotary switch (the red one shown above). For reference, 10 Mbps corresponds to position 4.

Configuring station numbers and other settings may seem complex at first, but once you have done it once it becomes clear. Start by confirming the station type, occupied station count, and CC-Link version for each device. The "QJ61BT11N" supports both Version 1 and Version 2. Versions 1 and 2 can coexist on the same network, so there is no need to worry about that detail. The version for each device is fixed by the device itself; refer to each device's manual. If even one device on the connected network is Version 2, configure the master as Version 2. Additionally, some devices change their occupied station count depending on the features used. For IAI controllers, half direct-value control occupies 2 stations, while full direct-value control occupies 4 stations. This is configured in advance in the IAI controller's parameters; the occupied station count is then determined by that setting. Station type is also fixed by the device. I/O terminal blocks are Remote I/O stations — stations that use only bit devices and do not require word devices. IAI controllers, which also use word devices, are Remote Device stations. Devices with a CPU such as a PLC are Intelligent Device stations. However, there is no need to memorize all of this — it is documented in each device's manual, so configure according to the manual. For occupied station counts, you can also call the device manufacturer's support center; they will tell you based on what features you need to use. This information is also in the manual.

The key point is that the occupied station count, version, etc. are not set freely by the master (PLC side) — they are determined by how the local device is used, and the PLC side simply registers the connected device's information. The same applies to the local station side. Local stations do not have an item for setting occupied station count (Intelligent Device stations are an exception). Local station settings typically consist only of station number and communication speed. Once you configure the local station's device parameters and determine how it will be used, the occupied station count, version, and scaling factor are determined automatically. Understand that occupied station count and version are not set by the PLC side — they are automatically determined by the device's functionality.

Once each local station's device settings are complete, assign the station numbers. The order in which station numbers are assigned does not matter — it does not need to match the physical CC-Link connection order. Assign them in any order you prefer.

Device 1:
Remote Device station, Ver.1
2 stations occupied

Device 2:
Remote Device station, Ver.1
2 stations occupied

CC-Link unit

In GX Works2, open the navigation panel and go to "Parameter" → "Network Parameter" → "CC-Link."

Opening CC-Link parameters in GX Works2 navigation

Enter the number of units and configure the device numbers for Remote Input (RX) and Remote Output (RY). Use larger numbers such as X400 and Y400 to avoid overlapping with standard I/O numbers.

CC-Link remote I/O device settings screen

Configure the remote registers in the same way. Assign a number such as "W100" for RWr and "W200" for RWw to make them easy to distinguish. RWr is data received from local stations (read-only); RWw is data sent to local stations (write-only).

When configuring CC-Link for the first time, it is strongly recommended to configure one unit at a time. Configuring all units at once makes it difficult to identify the cause when a device number assignment is off.

CC-Link station information settings screen (station type and occupied station count entry) Confirmation screen after completing CC-Link settings

After configuring, always verify the assignment using the "Device Usage List." Devices with an asterisk (*) in the parameter column are areas assigned by CC-Link.

Device usage list showing CC-Link assignment with * on X400 through X43F Device assignment verification for link registers W100 through W107

Device 1 assignment example:
Input devices: X400 to X43F
Output devices: Y400 to Y43F
Input word devices: W100 to W107
Output word devices: W200 to W207

I/O address verification screen Device assignment detail verification screen

Next, configure Device 2.

CC-Link station information settings for Device 2 CC-Link settings completion confirmation for Device 2

How to Verify Device Assignment

GX Works2 includes a convenient feature that displays the device assignment status in a list. Go to menu bar "View" → "Docking Window" → "Device Assignment Check."

GX Works2 device assignment verification window

A separate window opens. Enter the "First I/O No." in the upper left to view the assignment status of that unit in a list.

CC-Link device assignment verification list display

FAQ

What is CC-Link? Is ladder programming required?
CC-Link is a fieldbus network developed by Mitsubishi Electric that allows many devices to be connected with 4 cables. CC-Link connection is completed primarily through configuration settings rather than programming. No ladder diagram writing is required — configuration is done through GX Works2 parameter settings.
What is a CC-Link station number?
A station number is an address that identifies each device on the network. The master station (PLC) is assigned station number 0; local stations (slave stations) are assigned numbers 1 and above. Duplicate station numbers prevent a device from joining the network, so assign different numbers to each device.
How do I determine the occupied station count?
The occupied station count is determined by the device manufacturer and cannot be freely changed. It may vary depending on the features used (e.g., half direct-value control = 2 stations, full direct-value control = 4 stations). Check each device's manual or contact the manufacturer's support center.
What are the key points for configuring CC-Link for the first time?
It is important to configure one unit at a time and verify the assignment using the device usage list. Configuring all units at once makes it difficult to identify the cause when device numbers are misassigned. Also, set the same communication speed value on all connected devices.
PLC Sequence Control Course recommended materials banner

The "Illustrated Guide to the Latest Sequence Control and Circuit Diagrams" is available as a Kindle edition (ebook). If you prefer a paperback, please select the paperback format. Alternatively, you can purchase it from the top page.

PLC Sequence Control Course banner
Copyright (C) 2010 PLC Sequence Control Course, All rights reserved.